ClickCease
Request Quote

TD60-MC

Tan Delta Diagnostics System

The TD60-MC system uses wireless Bluetooth technology and has an extremely simple test set up making field testing a breeze. Compared to other large and bulky TD systems on the market that require several connections, the TD60-MC requires very few connections and interfaces easily with the HVA60 using a multi-connector (MC).

The TD60-MC is a great tool to trend cable data overtime to show gradual degradation decreasing operational risk. Defective and/or degraded terminations and splices, water treeing, concentric neutral wire corrosion, and installation defects can be detected with this instrument.

The TD60-MC is designed to work with the HVA60 VLF system and is therefore capable of performing diagnostic tests on 35kV cables and below. The unit comes in a custom case with rollers and a convenient, pull-out handle for easy transportation. The unit is supplied with host of accessories including corona protection, jumper cables, ground cable, D Type batteries, D Battery Charger etc. Learn more about Tan Delta testing here.

VLF Power Supply Required - Sold Separately

Features:

  • Perform advanced diagnostics on MV Cables according to IEEE400 and 400.2
  • Suitable for testing 35kV cables and below
  • Wireless Bluetooth Connection
  • Minimum connection hookups
  • Accurate 1E-5 Resolution!
  • Excellent, easy to use TD reporting
  • Supplied with Free TD control center Software and FW upgrades
  • Local LED indication for TD value range
  • Leakage Current Guard Protection
  • Sleep mode saves battery life
  • Uses universal C-type batteries
  • Supplied in rugged transport case with all accessories.

Measurements / Software

  • Info coming soon


Compatible VLF Hipots

Technical Specifications

Ordering Information:
706 003
Power Supply:
2 C Type Batteries
Rated Operating Voltage:

RMS
1-44kV
Peak
62kV
Voltage Measurement:

Resolution
0.1kV
Accuracy
1% (of reading)
Current: Measurement

Resolution
1µA
Accuracy
1% (of reading)
Frequency Measurement

Range
0.01 to 0.1Hz
Resolution
0.01Hz
Tan Delta / Dissipation Factor Measurement:

Resolution
1 x 10
-5
Accuracy >15nF
±1 x 10
-4
Accuracy <15nF
±3 x 10
-4
Minimum Load:
5nF
Weight:

11 lbs / 5 kgs
Dimensions:

(Length x Diameter)
18 x 5 inches / 450 x 125mm
Computer Interface:
Bluetooth™
Accessories Included:
Integrated HV and Grounding Cable
Bluetooth USB Dongle
TD Control Center Software
Operating Manual
Corona Protection
Standards:

Shock
IEC68-2-27
Vibration
IEC68-2-6
EMC
IEC6100-4-2, IEC6100-4-4, EN55011
Safety
EN60950, EN50191, EN61010-1
Environmental:

Storage
-13°F to 158°F / -25°C to 70°C
Operating
23°F to 113°F / -5°C to +45°C
Humidity
80% RH non-condensing

Note: Due to continuous development, the information may change without notice.

VLF / DC
Tan Delta
TD
Partial Discharge
PD
Oil
Testing
Cable
ID
Fault
Location