HVA30-7

Extra Power VLF / DC Hipot Tester

The HVA30-7 Extra Power VLF/DC Hipot model was designed primarily for electrical utilities that have large complex cable networks that demand a very powerful test instrument to overcome the large loads presented by these long cable systems.

Capable of testing up to 150,000ft / 45km of cable - it does not get much more powerful than this. This instrument, like all other HVA models, provides a very powerful high voltage DC output in addition to the VLF AC output.

The HVA30-7 model can be used for testing many other electrical apparatus like transformers, motors/generators, switchgear, etc. Its single piece design has one of the highest power-to-weight ratios outputs in the industry.

Like all other instruments in the HVA series, there is no need to connect two heavy pieces of test equipment with interconnecting cables, etc. There is no warm-up period required before use and no insulation oil used in the design that needs to be maintained.

Features:

  • Internal Storage of Test Reports
  • Download to PC and / or USB flash drive
  • Unlimited duty cycle
  • Flashover voltage detection
  • Bright backlit LCD display
  • Power supply immunity and independence
  • Low maintenance, oil-free design
  • HVA Control Center – User friendly software for immediate, professional detailed reporting and setup
  • Test your 25 (Maint), 15, 11, 8, 6.6, 5kV long MV cables
  • Test long cables up to ~ 150,000ft / 45km
  • Weighs only 125 lbs / 57kg.
  • Perform tests fully automatically
  • Real time oscilloscope display
  • Insulation Resistance & Cap. Measurement
  • RMS Metering of Current and Voltage
  • Output Frequency optimization

Output Modes

  • VLF Sinewave / Squarewave & DC outputs
  • DC ±34kV
  • Powerful VLF 34kVrms / 24kVpk output
  • Cable Jacket / Sheath testing
  • VLF Sinewave / Squarewave & DC outputs
  • DC ±34kV
  • Powerful VLF 34kVrms / 24kVpk output
  • Cable Jacket / Sheath testing

Safety

  • Remote interlock “kill switch” and HV status indication
  • Integrated internal discharge of DUT
  • 12kV power frequency voltage feedback protection


Optional Attachments

Technical Specifications

Ordering Information:
707 001
Power Supply/Input Voltage:
110 to 240V AC ±10% (50/60Hz)
Input Power Requirements:
1.5kVA@120V (limited)
3kVA @240V
Rated Max Output Voltage:

Sinusoidal RMS/Peak
34kV/24kV
Squarewave
34kV
DC
±34kV
Rate Max Output Current:

Sinusoidal RMS
85mA
DC/Squarewave
120mA
Output Frequency (default 0.1Hz):
0.01Hz to 0.1Hz adjustable small increment of 0.01Hz (10 frequencies)
Frequency Optimization:
Yes
Maximum Output Load Capability @ MAXIMUM voltage and frequency:
6µF
*60,000ft
*20km
Maximum Output Load Capability @ REDUCED voltage and/or frequency:
15µF
*150,000ft
*45km
Metering:

Voltage
0.1kV Resolution ±1% Accuracy
Current
1 µA Resolution ±1% Accuracy
Capacitance
0.1 nF to 20 µF Range
Resistance
0.1MΩ to 20GΩ Range
Timing
Included and integrated
Fast Arc/Flashover
Detection Included and Integrated
Waveform
Real time oscilloscope display of actual output voltage waveform
Output Mode (all load independent & symmetrical):
VLF AC Sinewave
VLF AC Squarewave
DC (both Positive and Negative Polarity)
Fault Condition Mode / Fault Trip Mode
Vacuum Bottle Test Mode (DC) - optional
Cable Jacket / Sheath Test Mode
Output Duty:
Continuous
Computer Interface:
RS232 Standard, USB Flash Memory Download Module (optional)

HVA Control Center Software included with every HVA instrument
Memory / Test Record Storage:

Built in Memory
50 Test Records
USB Flash Drive
Unlimited (see options)
No. of programmable Automatic Test Sequences:
40
Standard HV Test Lead Cable Included:
15ft / 4.5m
Weight:
125 lbs / 57 kg
Dimensions:

Imperial (inches)
18 x 13.5 x 20.5"
Metric (mm)
450 x 340 x 520 mm
Environmental:

Storage
-13°F to 158°F / -25°C to 70°C
Operating
23°F to 113°F / -5°C to +45°C
Humidity
85% RH non-condensing

* Based on typical MV cable. 100pf/ft or 330 pF/m

Note: Due to continuous development, the information may change without notice.