PD30-E

Partial Discharge Detection System

The PD30E is an ultra-compact partial discharge (PD) measurement and location system that interfaces to the HVA28TD, HVA34TD, HVA34, and HVA30-7 VLF AC test systems. The portable combination with the HVA28TD allows the user to perform VLF withstand, Tan Delta and Partial Discharge with one easy setup.

Diagnostics of medium and high voltage cables provides the opportunity for early detection of vulnerabilities and preventative maintenance work to be carried out before the cable fails in service.

Designed for testing cables up to 25kV class cables, the PD30E uses the same user friendly powerful software suite used in all our other PD systems and allows for both the detection and location mapping of PD activity in cable or device.

The PD30E comes complete in a rugged injection molded case with NIST traceable PD Calibrator. Learn more about Partial Discharge diagnostics here.

VLF Power Supply Required - Sold Separately


Features:

  • Weighs only 64 lb. / 29 kg (complete)
  • Battery or AC shore power operation
  • HVD Suite Software – for control and display
  • Extremely rugged and portable
  • Automatic and Manual Control of gain, trigger, and filtering options
  • Analog and Digital Noise mitigating algorithms and Filtering Options
  • Multiple Display format of PD Activity includes Phase Resolved Pattern, PD mapping, Raw signal, PD Intensity, PD Clusters, Voltage Dependence, Background Noise, etc.
  • Detection of PDIV and PDEV
  • Rated at 34kV Peak - ideal for cables rated 25kV & below for full Acceptance & Maintenance testing *in combination with the HVA34TD VLF/TD instrument (required, sold separately)
  • Rated at 34kV Peak (ideal for 25kV Maintenance and below rated cables)
  • Includes PD Calibration Instrument (acc. to IEC 60270)
  • While mainly used for testing cables, can also be used for testing switchgear, motors, coils, transformers, etc.
  • Quick and Easy reporting functionality
  • Corona protection toroids included
  • All cables and accessories included in the injection molded transport case with wheels and pull handle

Software: HVD Suite

  • Automatic or Manual Modes for PD Diagnostics
  • Sets or recommends measuring parameters for easy reporting
  • Guided Diagnostics Process & Comprehensive Data Bank
  • Requires MS Window 7/8 or later


Compatible VLF Hipots

Technical Specifications

Ordering Information:
700 221
Power Supply/Input Voltage
Internal Battery or 120-240V 50/60 Hz
Supply Power Required
20VA
Rated Max Voltage
0-34kV Peak / 24kV RMS @ 0.1Hz
Rated Max Current
1 Amp
Operating Frequencies
0.01 to 0.1Hz (Default 0.1Hz)
Filter Capacitance
4nF
Coupling Capacitance
1nF
Input Impedance

10kOhm / 50pF
Sampling Rate

125 MHz
Bandwidth

100 MHz
Measuring Range

12 miles @ 260 ft/uS
20 km @ 80 m/uS
Input Impedance

10kOhm / 50pF
PD Noise Sensitivity

5pC  (depends on environmental noise)
Voltages Synchronization

Automatic
Triggering

Manual and Automatic
Dimensions:

Imperial
12 x 19 x 10 in.
Metric
300 x 486 x 250 mm
Weight
64 lbs / 29 kg
Environmental:

Storage
-4F° to 150F° / -20C° to +65C°
Operating
23F° to 113F° / -5C° to 45C°
CALIBRATOR: PDC1 (ACC. IEC 60270)
(included with every PD30E system)
Ordering Information:
700 222
Output
100pC to 10 nC
Size and Weight
0.7 lb. @ 2.4” x 6.5” x 1.3”
0.3 kg @ 60mm x 164mm x 33mm
DIAGNOSTICS SOFTWARE: HVD SUITE
(included with all PD / PDTD systems)
Features
Automatic and Manual Control of HVA and PD Test System Fully Guided Measurement Process Storage Database PD Display – Raw Data, Calibration Pulse/s, PD Amplitude versus Distance, PD Amplitude versus Phase, PD Location (PD mapping), PDIV and PDEV, Automatic Distance to PD fault location, Noise and filtering options
Windows Compatible *
Windows 7, 8, 10 64 bit Operating Systems

* Note these are not included in scope of supply:

  • Laptop/PC is required to operate PD & PDTD – systems include Laptop/PC with order, unless otherwise specified.
  • An HVA Series VLF AC is required to operate with this instrument and is not automatically included.

Note: Due to continuous development, the information may change without notice.